| 정격 공급 전압 |
100 – 277 V |
| AC 전압 범위 |
100 – 320 V |
| 주 전원 주파수 |
50 / 60 Hz |
| Mode of protection |
L-N |
| AC system |
TN, TT or IT |
| Type 2 surge protection (T2) |
예 |
| Type 3 surge protection (T3) |
예 |
| Rated load current |
16 A |
| Nominal discharge current (8/20 µs) |
5 kA |
| Max. discharge current (8/20 µs) |
10 kA |
| Combination wave (1.2/50 µs) |
10 kV (5 kA) |
| Short-circuit current rating |
3 kA |
| Voltage protection level (at nominal discharge current (8/20 µs) and at 6 kV (1.2/50 µs)) |
≤ 1,3 kV |
| Residual voltage (at nominal discharge current (8/20 µs) and at combination wave (1.2/50 µs)) |
≤ 1,3 kV |
| TOV behavior (5 s / withstand mode) |
400 V AC |
| TOV behavior (120 min. / safe failure mode) |
528 V AC |
| Response time |
≤ 25 ns |
| Max. backup fuse (MCB type B and C) |
16 A |
| 주위 온도 ta |
-40 ... +80 °C |
| 보관 온도 ts |
-40 ... +80 °C |
| 보호 유형 |
IP20 |
| Altitude (above sea level) |
≤ 2.000 m |
| 치수 L x W x H |
56 x 36,5 x 34 mm |